Optimize the poll rate

This guide shows how to reduce the logging interval when samples are arriving too slowly.

Steps

  1. Go to Settings > Log.

  2. Lower the Poll interval value (the default is 250 ms).

  3. Click OK.

  4. Start logging and observe whether the actual sample rate meets the reduced interval.

If the interval is still slower than expected, the bottleneck is the Modbus protocol, not the poll timer. Apply the steps below.

Reduce Modbus overhead

Remove unused registers. Each additional register adds at least one Modbus request. Remove registers you do not need.

Group registers at consecutive addresses. ModbusScope reads consecutive addresses in a single packet. A gap between addresses forces a separate request. If your device allows it, arrange the registers you poll so their addresses are adjacent (e.g. 40001, 40002, 40003 rather than 40001, 40010, 40050).

Increase max consecutive registers per device. If your device can handle larger read requests, increase Max consecutive registers in Settings > Device. This allows ModbusScope to fetch more registers per packet when addresses are grouped.

Enable persistent connection (TCP only). When Persistent connection is off, ModbusScope opens and closes the TCP socket each poll cycle. Enabling it removes this overhead.

Result: After applying these changes, the effective sample rate should be closer to the configured poll interval.